HOTLink Rack Monitor

dc.creatorFranck, A. R.
dc.creatorGoodwin, R. W.
dc.creatorKasley, P. A.
dc.creatorShea, M. F.
dc.date2001-11-07
dc.date.accessioned2026-07-07T13:05:15Z
dc.date.available2026-07-07T13:05:15Z
dc.descriptionA remote data acquisition chassis, called a HOTLink Rack Monitor, HRM, has been developed for use in the Fermilab control system. This chassis provides for 64 analog input channels, 8 analog output channels, and 8 bytes of digital I/O. The interface to the host VMEbus crate is by way of a 320 MHz HOTLink serial connection to a PMC mezzanine module. With no processor intervention, all data sources in the remote chassis are read at 100 microsec intervals, timestamped, and stored in a 2 MB circular buffer on the PMC module. In operation, the memory always contains the most recent 16k samples of 10 kHz data from all 64 analog input channels. An expansion module that resides in the HRM chassis records snapshot data for 8 analog channels, each channel consisting of up to 16k readings, digitized at rates up to 10 MHz. Snapshot data is also returned and stored in buffers on the PMC module. Because the HRM presents a memory-mapped interface to the host, it is independent of the operating system and may be used in any system that supports PMC mezzanine modules.
dc.description3 pages, ICALEPCS-2001
dc.identifierhttps://arxiv.org/abs/physics/0111028
dc.identifierhttp://arxiv.org/abs/physics/0111028
dc.identifiereConf C011127:THAP047,2001
dc.identifier.urihttp://salesiana.dossiersoluciones.com/handle/123456789/227433
dc.subjectAccelerator Physics
dc.titleHOTLink Rack Monitor
dc.typetext