Transient stability of a power system with superconducting fault current limiters

dc.creatorSokolovsky, V.
dc.creatorMeerovich, V.
dc.creatorVajda, I.
dc.date2007-01-14
dc.date.accessioned2026-07-07T07:40:51Z
dc.date.available2026-07-07T07:40:51Z
dc.descriptionThe influence of a superconducting fault current limiter (FCL) on the transient stability of the synchronic operation of electric machines is analyzed for different locations of the inductive FCL in a network and for different parameters of the device. It is shown that the stability can be improved or degraded depending on the FCL impedance under a fault and the time of the recovery of the initial state of the limiter after a fault. Improving the transient stability with the inductive superconducting FCL is demonstrated in the experiments on the electrodynamic model of a power system. The expansion of the obtained results for other FCL designs is discussed.
dc.description12 pages, 7 figures
dc.identifierhttps://arxiv.org/abs/cond-mat/0701308
dc.identifierhttp://arxiv.org/abs/cond-mat/0701308
dc.identifier.urihttp://salesiana.dossiersoluciones.com/handle/123456789/121902
dc.subjectSuperconductivity
dc.titleTransient stability of a power system with superconducting fault current limiters
dc.typetext

Files

Collections